Drives and Automation > Useful Info > IP Rating > NEMA Class Existing members can log in.

NEMA Class

Below is a simple NEMA and IP Rating cross reference.
 
NEMA
enclosure
type no.


 
NEMA definition

IEC
enclosure
class


1

General-purpose. Protects against dust, light, and indirect splashing but is not dust-tight; primarily prevents contact with live parts; used indoors and under normal atmospheric conditions.
 
IP10

 
2


 
Drip-tight. Similar to Type 1 but with addition of drip shields; used where condensation may be severe (as in cooling rooms and laundries).

 
IP11

 
3 and 3S

 
Weather-resistant. Protects against weather hazards such as rain and sleet; used outdoors on ship docks, in construction work, and in tunnels and subways.

 
IP54

 
3R

 
Intended for outdoor use. Provides a degree of protection against falling rain and ice formation. Meets rod entry, rain, external icing, and rust-resistance design tests.

 
IP14

 
4 and 4X

 
Watertight (weatherproof). Must exclude at least 65 GPM of water from 1-in. nozzle delivered from a distance not less than 10 ft for 5 min. Used outdoors on ship docks, in dairies, and in breweries.

 
IP56

 
5

 
Dust-tight. Provided with gaskets or equivalent to exclude dust; used in steel mills and cement plants.

 
IP52

 
6 and 6P

 
Submersible. Design depends on specified conditions of pressure and time; submersible in water; used in quarries, mines, and manholes.

 
IP67

 
7

 
Hazardous. For indoor use in Class I, Groups A, B, C, and D environments as defined in the NEC.

 


 
8

 
Hazardous. For indoor and outdoor use in locations classified as Class I, Groups A, B, C, and D as defined in the NEC.

 


 
9

 
Hazardous. For indoor and outdoor use in locations classified as Class II, Groups E, F, or G as defined in the NEC.

 


 
10

 
MSHA. Meets the requirements of the Mine Safety and Health Administration, 30 CFR Part 18 (1978).

 


 
11

 
General-purpose. Protects against the corrosive effects of liquids and gases. Meets drip and corrosion-resistance tests.

 


 
12 and 12K

 
General-purpose. Intended for indoor use, provides some protection against dust, falling dirt, and dripping non corrosive liquids. Meets drip, dust, and rust resistance tests.

 
IP52

 
13

 
General-purpose. Primarily used to provide protection against dust, spraying of water, oil, and non corrosive coolants. Meets oil exclusion and rust resistance design tests.

 
IP54